Enhanced trend: S1 wired from wrong function code [ERROR 025]

Enhanced trend: S1 wired from wrong function code [ERROR 025]

Enhanced Trend: Module 1,01,02 Block 1001 S1 is wired from FC 30 Module 1,01,02 Block 1002 but S2 1 specifies FC 45

The indicated enhanced input is not a supported type. The documentation indicates that this is a configuration error.

From the documentation for ETREND: Enhanced Trend [FC179]:

S2 (Input block type) Identifies type of input to be trended.

  • 0 = function code 30, analog exception report
  • 1 = function code 45, digital exception report
  • 2 = function code 62, remote control memory
  • 3 = function code 68, remote manual set constant
  • 4 = function code 80, control station
  • 5 = function code 123, device driver
  • 6 = function code 129, multi state device driver
  • 7 = function code 136, remote motor control
  • 8 = function code 177, data acquisition analog
  • 9 = function code 211, data acquisition digital

The block addressed in S1 must match the input block type in S2 or a configuration error will result.

Enhanced Trend: Module 1,01,02 Block 1136 S1 is wired from FC 68 Module 1,01,02 Block 5131
but S2 0 specifies FC 30

No tool error reports 23.png

In this case, S1 is coming from the wrong type of block or S2 should be 3.

This message is likely to show an error in the system configuration. It should be reviewed. The issue raised may be in unused logic or graphics, or have other realities that make it a non-issue.

Please contact us for help resolving your error messages.