ASO/L: Analog Point Definition [FC70]

ASO/L: Analog Point Definition [FC70]


Specifications

Spec Description
S1Input type (see below)
S2EU type (see below)
S3EU identifier
S4Input zero
S5Input span
S6Significant change (percent of span)
S7High alarm limit
S8Low alarm limit
S9Lead wire resistance (ohms)

Format for S1-S2

Input Type

0Undefined
1TC type S
2TC type R
3TC type E
4TC type J
5TC type K
6TC type T
7Chinese TC type E
8Chinese TC type S
9Undefined TC types

EU Type

0Celsius
1Fahrenheit
2EU conversion
3Square root after EU conversion
4EU conversion after square root

Outputs

Block Type Description
N Real Measured point (EU)