TSTALM: Test Alarm [FC69]

TSTALM: Test Alarm [FC69]


Specifications

Spec Description
S1Block to be tested
S2
Alarm condition tested
0 = absolute
1 = deviation (stations) or LL/HH(DAANG)
2 = A/M (DD, MSDD) or 3L/3H (DAANG)

Outputs

For S2=0

Block Type Description
N Bit High alarm
N+1 Bit Low alarm (non-boolean blocks only)


For S2=1 with Station block (FC 80)

Block Type Description
N Bit High deviation alarm
N+1 Bit Low deviation alarm


For S2=1 with DAANG block (FC 177)

Block Type Description
N Bit HH or LL alarm
N+1 Bit HHH or LLL alarm


For S2=2 (Device drivers only)

Block Type Description
N Bit Alarm
N+1 Bit Manual/auto mode