Harmony I/O Module 1,01,02 Block 1001 FC 228 S2 wired from IREF NoSource with no source: module will compile but not run
This message means that the function block indicated cannot have an unwired input. If it does, Composer will allow it, but it will not run.
This undocumented issue was found by Ready Engineering when they inadvertently configured some Harmony I/O with empty input references.
Module 1,30,05 Block 198 FC 228 S3 wired from IREF (NB-1-30-05-01.08)with no source: module will compile but not run.
This message is likely to show an error in the system configuration. It should be reviewed. The issue raised may be in unused logic or graphics, or have other realities that make it a non-issue.