Segment control block check cycle time [ERROR 303]

Segment control block check cycle time [ERROR 303]

Segment Control Block Module 197,23,03 Block 1234 S2=0.1 minutes is greater than 2 seconds

Cycle time is unusually short or long.

The Function Code User Manual says this:

S2 – CYCTIM
Sets the target segment execution cycle in time units selected with the ones digit of S1. In each segment, blocks execute in a predefined order, selected with S15. A cycle consists of one execution of the blocks plus any idle time (cycle time remaining after the cycle has been executed). Cycle time is the length of time from the start of one cycle to the start of the next cycle.

This message is likely to show an error in the system configuration. It should be reviewed. The issue raised may be in unused logic or graphics, or have other realities that make it a non-issue.

Please contact us for help resolving your error messages.