Tag index not found in database [ERROR 123]

Tag index not found in database [ERROR 123]

Tag name TAGINDEX_06554 not found in database in MSDD31.DY

This message says that a tag was only identified by tag index, and that tag index was not found in the tag database. It can also refer to TRENDINDEX_nnnnn with the same sense. In both cases, there is no tag name to use, only a numerical index value that was not found in the assigned database.

This message should only apply to MCS and OIS SODG graphics, the most archaic form. PCView, WinTools and Conductor VMS all use tagname and trendname to make links.

However, the conversion from any SODG graphics system to Symphony Plus appears to need correct tag index values, so this error is very important if graphics are being cleaned up for conversion.

Example:

--Scanning graphic AC-T1 AIR COMPRESSOR TRND (AC-T1)
Tag name TAGINDEX_07631 not found in database  in trndpvfl.DY

This message is closely related to Build error 67: Tag name not found in any database

This message is likely to show an error in the system configuration. It should be reviewed. The issue raised may be in unused logic or graphics, or have other realities that make it a non-issue.

Please contact us for help resolving your error messages.